Authorized Channel · Bently Nevada Condition Monitoring Products & Services

Get a Quote · Tech Docs

3500/61 Thermocouple Temperature Monitor

Six-channel thermocouple temperature monitor supporting K/J/T types with a measurement range of -200 to +1300 °C.

Short answer

  • Six channels, thermocouple or RTD, with a 4–20 mA recorder output on every channel.
  • TC ranges: E −100 to +1000 °C, J −18 to +760 °C, K −18 to +1370 °C, T −160 to +400 °C.
  • Cold junction compensation is built in, specified at ±1 °C at 25 °C.
  • Recorder output: 0–600 Ω load, 0–12 V compliance. A shorted loop does not affect the module.
  • Same sensor support and accuracy as the 3500/60, but 9 W instead of 7 W.

Which thermocouple types does the 3500/61 support?

The 3500/61 accepts E, J, K and T thermocouples across six channels, with K reaching +1370 °C, E reaching +1000 °C, J reaching +760 °C and T reaching +400 °C. The J-type lower limit is −18 °C in the Bently Nevada datasheet, not 0 °C, so a specification quoting 0 °C is not matching the source document.

That −18 °C figure is the one most copied incorrectly, because −18 °C is 0 °F and the limit originates as an imperial figure. It rarely matters in a steam or exhaust application, but it does matter when someone is checking whether a module covers a cold-start condition.

Range selection is per channel, so one module can carry K-type exhaust thermocouples and T-type bearing temperature probes at the same time. The 3500/60 RTD monitor page covers the resistance side of the same platform, and the shared datasheet specifies both.

How does cold junction compensation work?

The module carries an internal cold junction sensor at the terminals and adds its reading to the thermocouple voltage, so the reported temperature is referenced to the actual terminal temperature rather than an assumed 25 °C. Compensation accuracy is ±1 °C at 25 °C, comparable to the module’s own accuracy, so it cannot be ignored in tight tolerances.

The practical consequence is that terminal temperature stability matters. A module mounted next to a heat source, or a termination assembly with poor air circulation, can introduce an offset that looks like a sensor error. This is why the specified accuracy is quoted at 25 °C with a stated termination arrangement rather than as an unconditional figure.

Input impedance is 10 MΩ per lead, which keeps a thermocouple’s own loop resistance from loading the measurement.

Is the recorder output the only difference from the 3500/60?

Yes, functionally. Both modules provide six channels, accept the same RTD types and the same E, J, K and T thermocouples, and share the same accuracy figures; the 3500/61 adds a 4–20 mA output per channel and its nominal power draw rises from 7 W to 9 W. There is no accuracy or range advantage to either card.

Item 3500/60 3500/61
Channels 6 6
RTD support Yes Yes
Thermocouple support E, J, K, T E, J, K, T
4–20 mA recorder output None Per channel, 0–600 Ω
Nominal power 7 W 9 W

The extra 2 W per module is worth checking on a full rack. Six temperature modules of the /61 type add 12 W over the equivalent /60 set, which is within a single 3500/15 supply’s capability but does change the rack thermal picture inside a sealed enclosure.

What happens if the recorder loop shorts?

A short on a recorder output does not affect module operation — the datasheet says so, so a fault in the DCS wiring cannot take down the protection channel. The output drives 4–20 mA into a load of 0–600 Ω with 0–12 V compliance, and a load above 600 Ω pushes the loop out of compliance.

That clause is more useful than it looks. In a plant where the temperature signal is daisy-chained into a marshalling cabinet, a shorted loop is a routine fault, and the assurance that the protection channel keeps working means the response can be scheduled rather than immediate. The limit to watch is the other direction: too much loop resistance, typically from long cable runs plus a non-ideal receiver, silently clips the top of the range.

If the trip action needs review while the module stays in place, the relay module specification covers contact ratings and voting logic, and the chassis page covers slot and power budgeting.

Frequently asked questions

Can a 3500/61 read an RTD instead of a thermocouple?

Yes. The module supports the same RTD set as the 3500/60, including Pt100 at both alpha values, Ni120 and Cu10, on any channel. A mixed installation of thermocouples and RTDs is possible on the non-isolated I/O version; check the fitted I/O type before configuring.

Do I have to change the module to add temperature trending?

If the trend has to travel as an analogue signal, yes. The 4–20 mA recorder output exists only on the 3500/61. Where temperatures are read digitally through the rack communication path, the 3500/60 already provides the values and no change is needed.

Why does the J-type range start at −18 °C?

Because the published limit is −18 °C, the Celsius equivalent of 0 °F. Specifications that quote 0 °C are rounding the imperial figure, which matters only when a cold-start condition below freezing has to be covered.

Sources

SpareTechHub supplies Bently Nevada 3500 temperature modules with and without recorder outputs. Send the module part number and the thermocouple types in service and we will confirm the correct variant — request a thermocouple module match.

Technical Specifications

Key Features6 thermocouple input channels (K/J/T); Measurement range -200 ~ +1300 °C; Accuracy ±0.5 °C
CertificationCE certified.
Model142276-01

Need a quote for this product (142276-01)?

Send us your required quantity and delivery timeline. We reply within 24 hours with factory-direct pricing. Worldwide shipping via DHL / FedEx / UPS / TNT.

Request a Quote or email [email protected] or call +86 167 4013 5928

Number of Channels6 channels
SensorThermocouple K / J / T
Measurement Range-200 ~ +1300 °C
Accuracy±0.5 °C
AlarmsFour-level alarms
Supply Voltage24 VDC