Short answer
- Four independent SPDT relays, epoxy sealed, with built-in 250 Vrms arc suppression.
- Contact rating is not a single number: 2 A at 0–30 Vdc, 0.75 A at 48 Vdc, 0.2 A at 125 Vdc.
- With SIL or hazardous-area approval the whole module is limited to 30 Vdc / 30 Vac at 2 A.
- Must be installed to the right of a 3500/22 TDI; the TDI is not optional.
- Each relay has its own Alarm Drive Logic, combining Alert, Danger, Not-OK and PPL with AND/OR.
What does the 3500/32 add to a protection rack?
The 3500/32 converts monitor alarm states into four dry contact outputs that can be wired to a DCS, an interlock or a field device, which is how a 3500 rack acts on a machine rather than only reporting on it. Each relay is independently configurable, so one module can serve four different trip or annunciation purposes without external logic.
Without a relay module, the rack knows a machine is in alarm but nothing outside the rack does. The 3500/32 is the boundary between protection logic and plant wiring, and that role explains why its contact ratings get more scrutiny than almost any other module specification.
Two constraints shape the design. The module must sit to the right of a 3500/22 TDI, because the interface module is what routes the relay drive signals, and each relay’s logic is configured rather than hardwired — Alert, Danger, Not-OK and PPL can be combined per relay in AND or OR form.
What can the relay contacts actually switch?
The contacts are rated 2 A at 0–30 Vdc, 0.75 A at 48 Vdc and only 0.2 A at 125 Vdc, with a 125 Vdc maximum and 250 Vac at 2 A or 450 VA. DC ratings fall steeply because arcs do not self-extinguish, so check a 125 Vdc trip coil against 0.2 A.
| Circuit | Rating |
|---|---|
| 0–30 Vdc | 2 A |
| 48 Vdc | 0.75 A |
| 125 Vdc | 0.2 A (125 Vdc maximum) |
| 250 Vac | 2 A, 450 VA |
| Minimum switching | 100 mA at 12 Vdc |
| SIL or hazardous-area use | Limited to 30 Vdc / 30 Vac, 2 A |
| Contact life | 100,000 operations at 5 A, 24 Vdc or 240 Vac |
Three numbers in that table are routinely misquoted. First, 2 A is a 30 Vdc figure and does not carry up the voltage scale. Second, 125 Vdc is a maximum, not a working value to design to. Third, the minimum switching current of 100 mA at 12 Vdc means a low-level input card cannot be driven reliably by these contacts — a relay that never sees enough current to wet the contacts can develop an oxide film and read open when it matters.
If the field device needs more than the contact can carry, the answer is an interposing relay rather than a different module. That is a normal design, not a workaround.
How is each relay’s logic configured?
Every relay has its own Alarm Drive Logic, an AND/OR combination of Alert, Danger, Not-OK and PPL inputs, and each can be set to energise or de-energise on alarm with optional latching. That per-relay independence is what lets one module drive a DCS alarm, a local annunciator, a trip solenoid and a spare output with four different behaviours.
The energise-to-trip versus de-energise-to-trip choice is a safety philosophy decision, not a preference. A de-energised-to-trip output fails safe on loss of power but will trip the machine if the rack loses supply; an energised-to-trip output does the opposite. Most plants standardise one convention and then meet the exception with a documented reason.
The Not-OK input deserves attention because it is easy to leave out of the logic. A relay that only looks at Alert and Danger will stay in its normal state when a transducer goes Not-OK, which is exactly the condition where the protection is blind.
Where must the 3500/32 sit in the rack?
The module must be installed in any slot to the right of the 3500/22 TDI, because the interface module provides the path the relay drive signals use. A rack built without a TDI has no way to place a relay module, so relay outputs and rack communications are added together rather than as separate upgrades.
This catches out retrofits where someone plans to add trip contacts to an existing rack and expects to drop a relay card into a free slot. The slot may be free; the prerequisite may not be fitted. The 3500/22M transient data interface page covers that module, and the 3500/05 chassis specification shows how the interface and power positions sit relative to the module slots.
Power draw is modest at 5.8 W typical, so a single relay module rarely changes the rack supply calculation. Four modules would, and that is worth checking against the supply budget if a large trip scheme is being added.
Frequently asked questions
Can a 3500/32 drive a 125 VDC trip coil directly?
Only if the coil draws 0.2 A or less, which is the contact rating at 125 Vdc. Most station trip coils draw more, so an interposing relay is the usual arrangement. Check the coil current rather than the coil voltage before deciding.
Does the 3500/32 require a 3500/22 TDI?
Yes. The relay module must be installed to the right of the TDI, and the TDI provides the drive path. A rack without a TDI cannot host the relay module even if a slot is physically free.
Are the relay contacts normally energised or normally de-energised?
Configurable per relay, together with optional latching. The choice is a safety philosophy decision: de-energise to trip fails safe on power loss but trips on supply failure, while energise to trip behaves the other way round.
Sources
- Baker Hughes, 3500/32M 4-Channel Relay Module Datasheet, 141533 — contact ratings by circuit voltage, SIL and hazardous-area derating, contact life, alarm drive logic and the TDI installation requirement.
SpareTechHub supplies Bently Nevada 3500 relay modules and interface modules for protection racks in service. Send the coil current and voltage of the device you intend to switch and we will confirm whether the contact rating covers it — request a relay application check.
Technical Specifications
| Key Features | 4 channels with DPDT contacts; Contact rating 250 VAC / 5 A; Programmable mapping for Danger / Alert / OK states |
|---|---|
| Certification | CE certified, meeting SIL 2 functional safety loop requirements. |
| Model | 125696-01 |