3500/15 Power Supply

24 VDC power supply with dual-power redundancy for powering the 3500 system rack.

Short answer

  • The 3500/15 is a half-height module that sits in the leftmost dedicated power positions of a 3500 rack. One supply carries a full rack; two give redundancy.
  • Universal AC input: 85–264 Vac in non-hazardous areas, 85–250 Vac in hazardous areas, 47–63 Hz.
  • DC versions: 88–140 Vdc high-voltage, 20–30 Vdc low-voltage.
  • AC and DC supplies can be mixed in one rack, and a supply can be replaced with the rack running if the second unit is in place.

What does the 3500/15 actually supply to a 3500 rack?

The 3500/15 converts a plant AC or DC feed into the regulated rails the 3500 backplane distributes to every module, and it is installed in dedicated half-height positions at the left of the rack rather than in a module slot. Power supply positions are separate from the 14 monitor slots, so adding redundancy never costs a measurement channel.

That last point is the one buyers most often get wrong when they size a rack. Redundancy is a power-slot decision, not a module-slot trade-off. The supply is a half-height card, which is why two of them occupy a single full-height bay at the left of the chassis.

One caution on ratings: the published 3500/15 datasheet (141530 Rev. P) specifies input ranges, input current and the Supply OK indication, but it does not publish an output voltage and current rating for the module. Vendor listings that quote a fixed “24 VDC / 5 A” figure are not reproducing a datasheet value. Size the supply from the module power budget and the input current figures below rather than from a copied output number.

Which input version do I need — AC, high-voltage DC or low-voltage DC?

Choose the version that matches the feed already in the cabinet, because the three variants are not interchangeable at the terminals: universal AC accepts 85–264 Vac, the high-voltage DC version accepts 88–140 Vdc, and the low-voltage DC version accepts 20–30 Vdc. A 24 V station battery therefore needs the low-voltage module, not the AC unit.

Version Input range Full-rack input current Current ordering number
Universal AC 85–264 Vac (non-hazardous); 85–250 Vac (hazardous); 120–373 Vac peak; 47–63 Hz 2.8 A rms max 106M1079-01
High-voltage DC 88–140 Vdc 2.5 A 114M5329-01
Low-voltage DC 20–30 Vdc 11.0 A 114M5330-01 (legacy 133292-01)

The low-voltage version draws 11 A at full rack load, which is roughly four times the AC figure — a detail that decides upstream breaker and cable sizing. It is also the reason a 24 V battery feed needs its own protection rather than sharing a lightly rated terminal block with instrumentation.

How does 3500/15 redundancy work?

Fit two supplies and the rack runs on the lower of the two with the upper as backup, so a single module failure does not drop the protection system. Either unit alone can carry a fully loaded rack, and because the supplies are half-height cards, a failed unit can be swapped while the rack stays powered by its partner.

The redundancy is deliberately simple, which is why it survives decades in service. Because one supply is sufficient for the whole rack, the second is not a capacity upgrade — it is availability. That framing helps when someone proposes deleting the second supply to save a slot: the slot costs nothing in measurement terms, and the second supply is what converts a single point of failure into a maintenance task.

Mixing an AC and a DC supply in one rack is permitted, and it is the standard way to ride through a station battery transfer. The lower position is the primary, so the unit you want as the normal source should be installed first.

Does 125800-01 still match the current catalogue?

125800-01 is not listed in the current 3500/15 datasheet, 141530 Rev. P, which instead shows 106M1079-01 for the universal AC version, 114M5329-01 for high-voltage DC and 114M5330-01 for low-voltage DC. Treat any 125800-01 quotation as a legacy or surplus article and confirm the input variant from the label before installing it in a live rack.

This is a common trap in spares procurement. A page or a quotation built from an older catalogue can carry a number that the current document no longer lists, and the risk is not that the module is bad — it is that the wrong input variant arrives. Check three things on the label: the input range, the approval marking, and whether the unit is the AC, high-voltage DC or low-voltage DC build.

If the rack itself is also being reviewed, the 3500/05 chassis specification explains how the power positions relate to the module slot count, and the 3500 support status note covers the platform’s long-term position.

Frequently asked questions

Can I mix an AC and a DC 3500/15 in the same rack?

Yes. The two supplies share the backplane and either can act as primary, which is why a mixed pair is used where a plant wants to ride through a battery transfer. Confirm the input range of each unit from its label, because the “3500/15” designation covers three different input builds.

Do I need two supplies for a full 14-slot rack?

No. A single 3500/15 is rated to carry a fully loaded rack, and the datasheet input currents above are quoted for that condition. The second supply is an availability decision rather than a capacity one, and it does not consume a monitor slot.

Is the power supply hot-swappable?

Yes, provided the second supply is in place and healthy. Removing the only supply in a live rack removes power from every module, so a single-supply installation should be treated as a planned outage for replacement.

Sources

  • Baker Hughes, 3500 Machinery Protection System — rack and power architecture.
  • Bently Nevada, 3500/15 AC and DC Power Supplies Datasheet, 141530 Rev. P — input ranges, input currents, dimensions, approvals, redundancy behaviour and current ordering numbers.

SpareTechHub supplies Bently Nevada 3500 power supplies in AC, high-voltage DC and low-voltage DC builds, new and surplus. Send the input range and approval marking from your existing unit and we will match the correct variant — request a power supply match.

Technical Specifications

Key FeaturesWide input range 85~264 VAC / 88~300 VDC; Output 24 VDC / 5 A; Dual-power redundancy supported
CertificationCE and CSA certified.
Model125800-01

Need a quote for this product (125800-01)?

Send us your required quantity and delivery timeline. We reply within 24 hours with factory-direct pricing. Worldwide shipping via DHL / FedEx / UPS / TNT.

Request a Quote or email [email protected] or call +86 167 4013 5928

Input Voltage85~264 VAC / 88~300 VDC
Output Voltage24 VDC
Output Current5 A
Redundancy SupportDual-power redundancy
Efficiency≥ 85 %
CertificationCE / CSA